GTL33 Low Frequency Online Uninterrupted Power Supply 10-600kva

This series of Uninterruptible power supply adopts DSP all-digital control technology with outstanding high stability and reliability. The standard industrial frequency output isolation transformer effectively suppresses and isolates the utility peak interference and load impact, and at the same time greatly improves the harmonic distortion of the load current, so that the load and the Uninterruptible power supply(ups) are in the optimal state.

Advanced rectifier and IGBT inverter control technology, on-line double conversion structure, more excellent performance.

Ultra-wide input voltage and frequency range for multiple systems, better grid adaptability.

Built-in output isolation transformer reduces the impact of zero ground voltage and load harmonics on the inverter.

Super load adaptability and output overload and short-circuit capability, perfect peak current protection technology, more stable operation.

Inquire Now
  • 10-600kVA three phase low frequency ups power supply-Gottogpower2
  • 10-600kVA three phase low frequency ups power supply-Gottogpower2

Share:

  • Introduction

  • Parameters

This series of Uninterruptible power supply adopts DSP all-digital control technology with outstanding high stability and reliability. The standard industrial frequency output isolation transformer effectively suppresses and isolates the utility peak interference and load impact, and at the same time greatly improves the harmonic distortion of the load current, so that the load and the Uninterruptible power supply(ups) are in the optimal state.

GTL33 series Uninterruptible power supply have powerful parallel redundancy characteristics and good remote monitoring and human-machine interface interactivity, as well as perfect detection and protection functions, which are the core guarantee for uninterrupted power supply in key scenarios of various industries.

    

Widely used in rail transportation, airport aviation, medical, oil, troops, radar stations, power, heavy industry, manufacturing production line and other fields.

Advanced rectifier and IGBT inverter control technology, on-line double conversion structure, more excellent performance.
Ultra-wide input voltage and frequency range for multiple systems, better grid adaptability.
Built-in output isolation transformer reduces the impact of zero ground voltage and load harmonics on the inverter.
Super load adaptability and output overload and short-circuit capability, perfect peak current protection technology, more stable operation.
Redundant design of control power system ensures high reliability and availability of Uninterruptible power supply(ups) control system.
Intelligent battery management design with automatic battery maintenance ensures the long service life of the battery.
Independent design of heat dissipation system, multiple protection inside and outside the system, ensuring the reliability of the system in harsh environments.
Supports dual utility or single utility input, so that the user's power supply is more securely guaranteed.
Friendly man-machine interface, colorful touch screen and keyboard combined use, convenient operation.

Model LT33010 LT33015 LT33020 LT33030 LT33040 LT33060 LT33080 LT33100 LT33120 LT33160 LT33200 LT33250 LT33300 LT33400 LT33500 LT33600
System  Capacity(kVA) 10 15 20 30 40 60 80 100 120 160 200 250 300 400 500 600
Input Input Voltage Waveform Sine wave
Rated Voltage Three-phase five-wire 380/400/415VAC
Voltage Range 285-475VAC
Number Of Phases 3P+N+PE
Rated Frequency 50Hz/60Hz
Frequency Range 45-65Hz
Bypass Static Bypass Transition Time 0ms
Bypass Input Range 380VAC(-15~+15%)
Frequency Range 50/60Hz±1Hz、±2Hz、±3Hz,ajustable
Frequency Tracking Speed 0.5~2Hz/s
Output Rated Voltage three phase 380VAC
Output Voltage Range 380VAC±1%
Output Power Factor 0.9
Voltage Phase Deviation ≤2°
Three-Phase Unbalance 100% unbalance allowed in three phases
Output Voltage Unbalance ≤1°(Balanced loads),≤2°(50%Balanced loads)
Output Waveform pure sine wave
Overload Capacity >125% overload runtime for 10 minutes; 150% overload for 60 seconds to bypass shutdown
Crest Factor 3:1
Battery Voltage Standard 384VDC, supports 28-32pcs 12V batteries Standard 384VDC, support 30-34pcs 12V batteries 480VDC, standard
Supports 38-42pcs 12V batteries
Type 2V or 12V maintenance-free lead-acid batteries
Backup Time Backup time determined by battery capacity
System Instant Recovery Time <20ms
Switching Time Utility ←→ Battery: 0ms; Utility ←→ Bypass: ≤2ms
Protection Grade IP20
Power Efficiency ≥90%
Eco Status ≥97%
Noise (2 Meters Away) <50-60dB
Grounding Method TN-S
Communication Interface Standard RS232/EPO/485/dry contact, SNMP (option)
Cooling Method air cooling
Case Color Black
Environment Ambient Temperature -10~40℃
Relative Humidity  0~95% Non-condensing
Altitude <1500m
Dimension
W*D*H(mm)
475*700*900 550*800*1000 605*800*1350 800*800*190C 1245*855*1900(6P)
1770*855*1900(12P)
1640*855*1900(6P)
2265*855*1900(12P)

2265*855

*1900(6P/12P)

2615*855

*1900(12P)

2865*955

*1900(12P)

Weight(kg) 210 223 23 280 330 450 550 630 750 1075(6P)
1685(12P)
1580(6P)
2090(12P)
2105(6P)
2500(12P)
2580 3130