HomeProductsThree Phase UPSGT33 Tower Online UPS Power Supply 80-600kVA
  • 600kVA tower type uninterruptible power supply Gottogpower

GT33 Tower Online UPS Power Supply 80-600kVA

100kVA 120kVA 180kVA 200kVA 240kVA 300kVA 400kVA 500kVA 600kVA Tower type Uninterruptible Power Supply(ups) 3P/3P,Online double conversion Application for Government, Finance, IT, Education, Transportation, Broadcasting, Medical, Energy, etc.

High power density, small volume.

High reliability and environment adaptibility.

32-44 batteries can be set

Inquire Now
  • 600kVA tower type uninterruptible power supply Gottogpower

Share:

  • Introduction

  • Parameters

  • 3P/3P pure online double transformation products, support 380 / 400 / 415V,
  • 50 / 60Hz power grid system, to providethe ideal power supply quality and load protection.
  • High performance and efficiency, inputPF>0.99,THDi<3%, efficiency >96%.
  • Full DSP control, flexible and robust digital control for rectifier, inverter and battery management.
  • Wide range of voltage and frequency,adapt to different grid and generator input.
  • Intelligent system self-diagnosis scheme,rich fault recording, large capacity ofhistory record storage space.
  • Redundancy fan design in power module,increasing the system reliability and tolerance.
  • Top/bottom cable entry, flexible for different field installation.
Tower UPS capacity100-600kVA

GOTTOGPOWER GT33 high-power series of high-quality power products, innovative design makes this series of products extremely reliable and high-performance. The extremely high input power factor and extremely low input current distortion rate ensure the greenness and environmental protection of the product, and the extremely high overall machine efficiency ensures the energy saving of the product.

Model GT33100T GT33120T GT33180T GT33200T GT33240T GT33300T GT33400T GT33500T GT33600T
Rate Power 100kVA 120kVA 180kVA 200kVA 240kVA 300kVA 400kVA 500kVA 600kVA 
Main
input
Input 3P5W (3P+N+PE)
Rate Voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
Rate Freq. 50/60Hz
Input PF >0.99
Current distortion THDi<3%(100% Linear load)
Voltage range 304 478VAC(L-L)full load 304 228VAC (L-L) power derate from 100% to 75%
Battery Rate voltage ±240VDC
Charging capacity 20%*Pout
Charging accuracy ±1%
Bypass Rate voltage 380/400/415VAC(L-L)220/230/240VAC(L-N)
Voltage range Range: -40%- +25% , Settable, default -20% +15%
Overload

125%, long time operation 125%< load <130%, 10mins
130%<load <150%,1min >150%,300ms

110%, long time operation 110%< load<125%, 5 mins
125%<load<150%,1 min >150%,1 second
Inverter Rate voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
Rate Freq. 50/60Hz
Output PF 1
Voltage accuracy ±1.0%
Load response <5% (20% - 80% -20% step load)
Recovery time < 20ms (0% - 100% -0% step load)
Output THDu <1%(linear load),<5% (non-linear load according to IEC 62040-3)
Overload 110%,1 hour 125%,10 mins 150%,1 min >150%,200ms
Frequency accuracy 0.001
Synchronize window Settable ±0.5Hz-±5Hz default ±3Hz
Slew rate Settable 0.5Hz/S-3Hz/S default 0.5Hz/S
Crest factor 3:1
Phase Accuracy 120°±0.5
System Efficiency Normal Mode≥96%;Battery mode≥96%
Display LED + 7 inch touch LCD LED + 10 inch touch LCD
Certification- Safety IEC62040-1, IEC60950-1
Certification- EMS IEC62040-2 IEC61000-4-2(ESD) IEC61000-4-3(RS) IEC61000-4-4 (EFT) IEC61000-4-5 (Surge)
IP degree IP20
Configuration USB, RS232, RS485, Dry contact, Cold start, Air filter
Option SNMP card, AS400 card, Parallel kit, SPD, LBS
Environment 0-40 (operation) -25 ~70 (storage) 0-95% (Humidity, non-condensing)
Noise(dB)(1 meter) 72dB @ 100% load, 69dB @ 45% load
Dimension
(W*D*H) mm
External batteries 600*1000*1600 600*1000*2000 1200*1100*2000

Consulting Products

Free to contact us