HomeProductsSingle Phase UPSGT31 Tower Online Uninterruptible Power Supply 10kVA 15kVA 20kVA
  • 10-20kVA 3phase high frequency uninterruptible power supply tower type-Gottogpower
  • 10-20kVA 3phase high frequency uninterruptible power supply tower type-Gottogpower(2)

GT31 Tower Online Uninterruptible Power Supply 10kVA 15kVA 20kVA

Power range:10~20kVA Operation:3/1,online double conversion Applications:Government, Finance, IT, Education, Transportation, Broadcasting, Medical, Energy, etc.

Small size with higher power density

Digital Charger, adjustable from 1A to 5A

12A charger for option, charging for large capacity batteries

Full protection of overvoltage, circuit short and over temperature

Inquire Now
  • 10-20kVA 3phase high frequency uninterruptible power supply tower type-Gottogpower
  • 10-20kVA 3phase high frequency uninterruptible power supply tower type-Gottogpower(2)

Share:

  • Introduction

  • Parameters

  • GOTTOGPOWER three Phase in Single Phase Out Tower Uninterruptible Power Supplies(UPS) 10kVA 15kVA 20kVA
  • Power range:10~20kVA
  • Operation:3/1,online double conversion
  • Applications:Government, Finance, IT, Education, Transportation, Broadcasting, Medical, Energy, etc.
  • Intelligent battery management.
  • 3-level topology, high performance and efficiency.
  • Online double conversion, full digital control.
  • Output PF=1,high load adaptability.
  • Wide range of input voltage tolerance.
  • Adapt to half-wave load.
  • Auto fault waveform recording.
  • Self-aging function to save test energy.
Model GT31010TL GT31015TL GT31020TL
Rate Power 10kVA 15kVA 20kVA
Cold start Default output 50/60Hz
Input voltage range 190~499VAC(L-L)
Input power factor 0.99
Frequency range 40-70Hz
Output frequencyOutput power factor 50/60Hz,self adaption
Output power factor 1
Rate output 220/230/240VAC
Load regulation ±1%
Output THDu 1%,Linear load ;3%,non-linear load according to IEC62040-3
Transfer time-INV to BYP 0ms
Efficiency- normal mode Max 95%
Efficiency- ECO mode 98%
Noise (1 meter) <55dB <62dB <62dB
Overload (normal mode) 110%: 10mins; 125%: 1min; 150%: 30 seconds
Battery Model External batteries, 16-24 settable
Quantity
Max charging 5A
Rate voltage Default 192VDC, settable
Crest factor 3:1
Standard RS232, RS485, EPO
Option AS400, SNMP card, Parallel kit, USB, 12A charger, Air filter, Single Input kit, Maintenance bypass kit
Dimension,(W*D*H)mm 90*554*338 190*564*550 190*564*550
Weight (kg) 20 30 30

Consulting Products