HomeProductsModular Online UPSGT-50SPM Smart Modular Online UPS power supply 200/300/600kVA(3/3)
  • 600kVA 50power module uninterruptible power supply smart modular-Gottogpower
  • 300kVA 50power module uninterruptible power supply smart modular-Gottogpower

GT-50SPM Smart Modular Online UPS power supply 200/300/600kVA(3/3)

200kVA 300kVA 600kVA Smart Modular Uninterruptible Power Supply(ups) 3P/3P,Online double conversion Application for Government, Finance, IT, Education, Transportation, Broadcasting, Medical, Energy, etc.

Fully digital control, flexible and robust.

7 &10 inch touch LCD, with IoT functions

High reliability and environment adaptability, with protection of components level.

Intelligent system self-diagnosis, rich fault recording, large capacity of history record storage space.

Maximum system capacity up to 1.8MVA, the best solution for mega data center.

Inquire Now
  • 600kVA 50power module uninterruptible power supply smart modular-Gottogpower
  • 300kVA 50power module uninterruptible power supply smart modular-Gottogpower

Share:

  • Introduction

  • Parameters

Full-load-temperature-rise-test
Modular-UPS-ultra-high-system-efficiency
Power-module-distribution-diagram

GOTTOGPOWER Modular Uninterruptible power supply(ups) GT-50SPM series highly integrated new PCB design, truly achieving minimalist assembly, reasonable power and signal layout, reducing signal interference, improving heat dissipation efficiency and design margin.

Compatible with upperlower incoming and outgoing lines
Compatible with upperlower incoming and outgoing lines(1)
Compatible with upperlower incoming and outgoing lines(2)

Compatible with upper/lower incoming and outgoing lines

IoT-application-scenarios-1
IoT-application-scenarios-2

IoT application scenarios for all Modular UPS

Model GT200/50SPM GT300/50SPM GT600/50SPM
Rate Power 200kVA/200kW 300kVA/300kW 600kVA/600kW
Main
input
Input 3P5W (3P+N+PE)
Rate Voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
Rate Freq. 50/60Hz
Input PF >0.99
Current distortion THDi<3%(100% Linear load)
Voltage range 304 478VAC(L-L)full load 304 228VAC (L-L) power derate from 100% to 75%
Freq. range 40-70Hz
Battery Rate voltage ±240VDC
Charging capacity 20%*Pout
Charging accuracy ±1%
Bypass Rate voltage 380/400/415VAC(L-L)220/230/240VAC(L-N)
Voltage range Range: -40%- +25% , Settable, default -20% +15%
Overload 125%, long time operation125%< load<130%, 10 mins
130%<load<150%,1 min>150%,300 ms
110%, long time operation110%< load<125%, 5 mins
125%<load<150%,1 min
>150%,1 second
Inverter Rate voltage 380/400/415VAC(L-L) 220/230/240VAC(L-N)
Rate Freq. 50/60Hz
Output PF 1
Voltage accuracy ±1.0%
Load response <5% (20% - 80% -20% step load)
Recovery time < 20ms (0% - 100% -0% step load)
Output THDu <1%(linear load),<5% (non-linear load according to IEC 62040-3)
Overload 110%,1 hour 125%,10 mins 150%,1 min >150%,200ms
Frequency accuracy 0.001
Synchronize window Settable ±0.5Hz-±5Hz default ±3Hz
Slew rate Settable 0.5Hz/S-3Hz/S default 0.5Hz/S
Crest factor 3:1
Phase Accuracy 120°±0.5
System Efficiency Normal Mode96%;Battery mode96%
Display LED + 7 inch touch LCD LED + 10 inch touch LCD
Certification- Safety IEC62040-1, IEC60950-1
Certification- EMS IEC62040-2 IEC61000-4-2(ESD) IEC61000-4-3(RS) IEC61000-4-4 (EFT) IEC61000-4-5 (Surge)
IP degree IP20
Configuration USB, RS232, RS485, Dry contact, Cold start,Air filter
Option SNMP card, AS400 card, Parallel kit, LBS
Environment 0-40 (operation) -25 ~70 (storage) 0-95% (Humidity, non-condensing)
Noise(dB)(1 meter) 72dB @ 100% load, 69dB @ 45% load
Dimention cabinet(W*D*H)mm 600*1000*1600 600*1000*2000 1200*1100*2000
module(W*D*H)mm 440*659*174

Consulting Products