Modèle |
GT33090B/30-240 |
GT33150B/30-240 |
Puissance nominale |
90kVA |
150kVA |
Maininput |
Saisir |
3P5W(3P+N+PE) |
Tension nominale |
380/400/415VAC(L-L);220/230/240VAC(L-N) |
Taux Fréq. |
50/60Hz |
Entrée PF |
>0,99 |
Distorsion actuelle |
THDi<3%(100%Linear load) |
Plage de tension |
304~478VAC(L-L)full load;304~228VAC(L-L)power derate from 100%to 75% |
Freq.range |
40-70 Hz |
Batterie
|
Tension nominale |
±240 VCC |
Modèle |
UPS with intemal batteries,12VDC/7~9Ah |
Quantité |
240PCS |
Capacité de charge |
20%*Boue |
Précision de charge |
±1% |
Contourne |
Tension nominale |
380/400/415 VCA (LL)220/230/240 VCA (LN) |
Plage de tension |
Range:-40%-+25%,Settable,default-20%~+15% |
Gamme de fréquences |
50/60Hz,Settable:±1Hz,±3Hz,±5Hz |
Onduleur |
Tension nominale |
380/400/415VAC(L-L);220/230/240VAC(L-N) |
Taux Fréq. |
50/60Hz |
Sortie PF |
1 |
Précision de la tension |
±1,0% |
Réponse de charge |
<5%(20%-80%-20% step load) |
Le temps de récupération |
<20ms (0%-100%-0% step load) |
Sortie THDu |
<1%(linear load),<5%(nonlinear load according to IEC 62040-3) |
Surcharge |
110%,1 hour;125%,10 mins;150%,1 min;>150%,200ms |
Précision de la fréquence |
0.1% |
Synchroniser la fenêtre |
Settable,±0.5Hz-±5Hz,default ±3Hz |
Vitesse de balayage |
Settable,0.5Hz/S-3Hz/S,default 0.5Hz/S |
Facteur de crête |
3:1 |
Précision des phases |
120°±0.5° |
Système |
Efficacité |
Normal Mode up to 96%;Battery Mode up to 96% |
Afficher |
LED+10 inch touch LCD |
Certification-Safety |
IEC62040-1,IEC60950-1 |
Certification-EMS |
IEC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);IEC61000-4-4(EFT);IEC61000-4-5(Surge) |
Diplôme IP |
IP20 |
Configuration |
USB,RS232,RS485,Dry contact,Air filter |
Option |
SNMP card,AS400 card,Parallel kit,LBS,Cold start |
Environnement |
0-40℃(operation);-25℃~70℃(storage);0-95%(Humidity,non-condensing) |
Dimension |
Cabinet (W*D*H)mm |
600*1000*2000 |
Module(W*D*H)mm |
440*678*86(2U) |
Poids (kg) |
Cabinet(No include batteries) |
260 |
280 |
Module |
23 |
Power module rated capacity |
30KW |