HomeProductsModular Online UPSGT-36LPM 208V Modular Online UPS 144/216/360kVA(3/3)
  • 360kVA 36power module uninterruptible power supply smart modular-Gottogpower208v
  • 36PM power module for smart modular UPS power supply

GT-36LPM 208V Modular Online UPS 144/216/360kVA(3/3)

144kVA 216kVA 360kVA Smart Modular Uninterruptible Power Supply(ups) 208VAC,meet the requirements of Europe and America 3P/3P,Online double conversion Application for Government, Finance, IT, Education, Transportation, Broadcasting, Medical, Energy, etc.

Fully digital control, flexible and robust.

7 &10 inch touch LCD, with IoT functions

High reliability and environment adaptability, with protection of components level.

Intelligent system self-diagnosis, rich fault recording, large capacity of history record storage space.

Maximum system capacity up to 1.8MVA, the best solution for mega data center.

Inquire Now
  • 360kVA 36power module uninterruptible power supply smart modular-Gottogpower208v
  • 36PM power module for smart modular UPS power supply

Share:

  • Introduction

  • Parameters

Full-load-temperature-rise-test
Power-module-distribution-diagram

In order to achieve minimalist assembly, the modular uninterruptible power supply (UPS) PCB design is highly centralized. In order to reduce signal interference, improve heat dissipation efficiency and design margin, the power supply and signals are reasonably laid out. The above curve chart serves as our detection standard. for reference

Compatible with upperlower incoming and outgoing lines
Compatible with upperlower incoming and outgoing lines(1)
Compatible with upperlower incoming and outgoing lines(2)

Compatible with upper/lower incoming and outgoing lines

The following is a professional wiring installation diagram for reference. It is simple to install, neat and easy to manage.

UPS cabling installation diagram
UPS cabling installation diagram(2)
UPS cabling installation diagram(3)
Model GT144/36LPM GT216/36LPM GT360/36LPM
Rate Power 144kVA/144kW 216kVA/216kW 360kVA/360kW
Main
input
Input 3P5W (3P+N+PE)
Rate Voltage 200/208/220VAC(L-L)
Rate Freq. 50/60Hz
Input PF >0.99
Current distortion THDi<3%(100% Linear load)
Voltage range 166-261VAC(L-L)full load; 125-166VAC (L-L) power derate from 100% to 75%
Freq. range 40-70Hz
Battery Rate voltage ±120VDC
Charging capacity 20%*Pout
Charging accuracy ±1%
Bypass Rate voltage 200/208/220VAC(L-L)
Voltage range Range: -40%- +25% , Settable, default -20% +15%
Overload 125%, long time operation125%< load<130%, 10 mins
130%<load<150%,1 min>150%,300 ms
110%, long time operation110%< load<125%, 5 mins
125%<load<150%,1 min
>150%,1 second
Inverter Rate voltage 200/208/220VAC(L-L)
Rate Freq. 50/60Hz
Output PF 1
Voltage accuracy ±1.0%
Load response <5% (20% - 80% -20% step load)
Recovery time < 20ms (0% - 100% -0% step load)
Output THDu <1%(linear load),<5% (non-linear load according to IEC 62040-3)
Overload 110%,1 hour 125%,10 mins 150%,1 min >150%,200ms
Frequency accuracy 0.001
Synchronize window Settable ±0.5Hz-±5Hz default ±3Hz
Slew rate Settable 0.5Hz/S-3Hz/S default 0.5Hz/S
Crest factor 3:1
Phase Accuracy 120°±0.5
System Efficiency Normal Mode93%;Battery mode93%
Display LED + 7 inch touch LCD LED + 10 inch touch LCD
Certification- Safety IEC62040-1, IEC60950-1
Certification- EMS IEC62040-2 IEC61000-4-2(ESD) IEC61000-4-3(RS) IEC61000-4-4 (EFT) IEC61000-4-5 (Surge)
IP degree IP20
Configuration USB, RS232, RS485, Dry contact, Cold start,Air filter
Option SNMP card AS400 card Parallel kit SPD LBS
Environment 0-40 (operation) -25 ~70 (storage) 0-95% (Humidity, non-condensing)
Noise(dB)(1 meter) 72dB @ 100% load, 69dB @ 45% load
Dimention cabinet(W*D*H)mm 600*1000*1600 600*1000*2000 1200*1100*2000
module(W*D*H)mm 440*659*174

Consulting Products

Free to contact us