HomeProductsSingle Phase UPSGTL31 Low Frequency Online Uninterrupted Power Supply 6-30kva
  • 6-30kVA single phase low frequency ups power supply Gottogpower

GTL31 Low Frequency Online Uninterrupted Power Supply 6-30kva

GTL31 Low Frequency 6-30kva series Uninterruptible power supply is a three-phase input/single-phase output small and medium power, pure on-line UPS with full digital control technology, with parallel redundancy function of the uninterruptible power supply products, standard frequency output isolation transformer will be effectively suppressed and isolated from the utility power spike interference and load impact.

Advanced rectifier and IGBT inverter control technology, on-line double conversion structure, more excellent performance.

Ultra-wide input voltage and frequency range for multiple systems, better grid adaptability.

Built-in output isolation transformer reduces the impact of zero ground voltage and load harmonics on the inverter.

Inquire Now
  • 6-30kVA single phase low frequency ups power supply Gottogpower

Share:

  • Introduction

  • Parameters

GTL31 Low Frequency 6-30kva series Uninterruptible power supply is a three-phase input/single-phase output small and medium power, pure on-line UPS with full digital control technology, with parallel redundancy function of the uninterruptible power supply products, standard frequency output isolation transformer will be effectively suppressed and isolated from the utility power spike interference and load impact, and at the same time, can greatly improve the harmonic distortion of the load current, so that the load and the UPS is in the best state of cooperation.

Rail transportation, airports and aviation, medical, oil, troops, radar stations, power, heavy industry sites, manufacturing lines, etc.

Advanced rectifier and IGBT inverter control technology, on-line double conversion structure, more excellent performance.
Ultra-wide input voltage and frequency range for multiple systems, better grid adaptability.
Built-in output isolation transformer reduces the impact of zero ground voltage and load harmonics on the inverter.
Super load adaptability and output overload and short-circuit capability, perfect peak current protection technology, more stable operation.
Intelligent battery management design, automatic battery maintenance, ensures the long service life of the battery.
Independent design of heat dissipation system, multiple protection inside and outside the system, ensuring the reliability of the system under harsh environment.
Independent battery interface avoids installation errors and greatly reduces the risks caused by misuse.
Friendly man-machine interface, color touch screen and keyboard are combined for convenient operation.
Standard with self-locking universal roller design, easy to move and ensure the installation is fixed.

Model LT3106L LT3110L LT3115L LT3120L LT31301
Capacity(kVA) 6 10 15 20 30
Character System Double conversion in-line
Machine structure Designed with output isolation transformer
Whole machine full load efficiency >85%
Noise (2 meters away) <50dB
Working temperature -10-40℃
Storage temperature -25-60℃(excluding in-unit battery)
Humidity <95%non-condensing
Redundant Paralleling Support
Protection function Overload, short-circuit, over-temperature, utility over/under, battery over/under
DC start function Support
Protection class IP20
Heat dissipation system Speed control fan air-cooled
Altitude <1000m without capacity reduction
Input Input Voltage 380VAC+N+W three phase
Input voltage range 286-475VAC
Input frequency range 50Hz±5%
Slow start > 2 0 s
Inverter Output voltage 220VAC
Output power factor 0.8
Output Voltage Stability 220VAC±1%(static load),220VAC±2%(100-0%load jump)
Output Frequency 50Hz±0.1%(with battery operation)
Distortion <1%(linear full load),<3%(100% nonlinear load)
Frequency tracking range 46-54Hz
Output Waveform Pure sine wave
Overload 125% load runtime >10 minutes; >150% load runtime >1 minute to bypass shutdown
Peak Factor 3:1
Bypass Static Bypass Transition Time 0ms(static switching phase-locked control technology)
Static Bypass Overload Capability 200%~5min;1000%~10s
Frequency Range ±1Hz、±2Hz、±3Hz ajustable
Manual Maintenance Bypass Support
Alarm Alarm Utility power abnormality or failure, low/high battery voltage, overload, UPS failure, short circuit, etc.
Mute Automatic
Battery Battery Type Sealed lead-acid maintenance-free battery
Battery Voltage 384VDC (10-20kVA can be customized 192VDC/16pcs)
Number of Cells per Battery 32pcs(32-28pcs optional)
Charge Current long 15A
Battery Low Shutdown protection
Interface Communication Interface Standard RS232/USB/EPO;SNMP/485/dry contact(option)
Dimenison  mm(W*D*H) 310*670*820
Weight  kg 67 74 99 117 125

Consulting Products