Model |
GT030/15PM |
GT060/15PM |
GT90/15PM |
Rate Power |
30kVA/30kW |
60kVA/60kW |
90kVA/90kW |
Main
input |
Input |
3P5W (3P+N+PE) |
Rate Voltage |
380/400/415VAC(L-L) 220/230/240VAC(L-N) |
Rate Freq. |
50/60Hz |
Input PF |
>0.99 |
Current distortion |
THDi<3%(100% Linear load) |
Voltage range |
304 478VAC(L-L)full load 304 228VAC (L-L) power derate from 100% to 75% |
Freq. range |
40-70Hz |
Battery |
Rate voltage |
±240VDC |
Charging capacity |
20%*Pout |
Charging accuracy |
±1% |
Bypass |
Rate voltage |
380/400/415VAC(L-L)220/230/240VAC(L-N) |
Voltage range |
Range: -40%- +25% , Settable, default -20% +15% |
Overload |
110%, long time operation;110%< load<125%, 5 mins;
125%<load<150%,1 min;>150%,1 second |
Inverter |
Rate voltage |
380/400/415VAC(L-L) 220/230/240VAC(L-N) |
Rate Freq. |
50/60Hz |
Output PF |
1 |
Voltage accuracy |
±1.0% |
Load response |
<5% (20% - 80% -20% step load) |
Recovery time |
< 20ms (0% - 100% -0% step load) |
Output THDu |
<1%(linear load),<5% (non-linear load according to IEC 62040-3) |
Overload |
110%,1 hour 125%,10 mins 150%,1 min >150%,200ms |
Frequency accuracy |
0.001 |
Synchronize window |
Settable ±0.5Hz-±5Hz default ±3Hz |
Slew rate |
Settable 0.5Hz/S-3Hz/S default 0.5Hz/S |
Phase Accuracy |
120°±0.5 |
System |
Efficiency |
Normal Mode≥96%;Battery mode≥96% |
Display |
LED + 7 inch touch LCD |
Certification- Safety |
IEC62040-1, IEC60950-1 |
Certification- EMS |
IEC62040-2 IEC61000-4-2(ESD) IEC61000-4-3(RS) IEC61000-4-4 (EFT) IEC61000-4-5 (Surge) |
IP degree |
IP20 |
Configuration |
USB, RS232, RS485, Dry contact, Cold start |
Option |
SNMP card, AS400 card, Parallel kit, LBS, Air filter, Bottom entry kit, Wheels kit |
Environment |
0-40 (operation) -25 ~70 (storage) 0-95% (Humidity, non-condensing) |
Noise(dB)(1 meter) |
65dB @ 100% load, 62dB @ 45% load |
Dimention |
cabinet(W*D*H)mm |
482*700*396 (9U wheels not included) |
482*700*662(15U wheels not included) |
482*700*840(19U wheels not included) |
module(W*D*H)mm |
440*555*85 (2U) |