Model |
GT33090B/30-240 |
GT33150B/30-240 |
Rate Power |
90kVA |
150kVA |
Maininput |
Input |
3P5W(3P+N+PE) |
Rate Voltage |
380/400/415VAC(L-L);220/230/240VAC(L-N) |
Rate Freq. |
50/60Hz |
Input PF |
>0.99 |
Current distortion |
THDi<3%(100%Linear load) |
Voltage range |
304~478VAC(L-L)full load;304~228VAC(L-L)power derate from 100%to 75% |
Freq.range |
40-70Hz |
Battery
|
Rate voltage |
±240VDC |
Model |
UPS with intemal batteries,12VDC/7~9Ah |
Quantity |
240PCS |
Charging capacity |
20%*Pout |
Charging accuracy |
±1% |
Bypass |
Rate voltage |
380/400/415VAC(L-L)220/230/240VAC(L-N) |
Voltage range |
Range:-40%-+25%,Settable,default-20%~+15% |
Frequency range |
50/60Hz,Settable:±1Hz,±3Hz,±5Hz |
Inverter |
Rate voltage |
380/400/415VAC(L-L);220/230/240VAC(L-N) |
Rate Freq. |
50/60Hz |
Output PF |
1 |
Voltage accuracy |
±1.0% |
Load response |
<5%(20%-80%-20% step load) |
Recovery time |
<20ms (0%-100%-0% step load) |
Output THDu |
<1%(linear load),<5%(nonlinear load according to IEC 62040-3) |
Overload |
110%,1 hour;125%,10 mins;150%,1 min;>150%,200ms |
Frequency accuracy |
0.1% |
Synchronize window |
Settable,±0.5Hz-±5Hz,default ±3Hz |
Slew rate |
Settable,0.5Hz/S-3Hz/S,default 0.5Hz/S |
Crest factor |
3:1 |
Phase Accuracy |
120°±0.5° |
System |
Efficiency |
Normal Mode up to 96%;Battery Mode up to 96% |
Display |
LED+10 inch touch LCD |
Certification-Safety |
IEC62040-1,IEC60950-1 |
Certification-EMS |
IEC62040-2;IEC61000-4-2(ESD);IEC61000-4-3(RS);IEC61000-4-4(EFT);IEC61000-4-5(Surge) |
IP degree |
IP20 |
Configuration |
USB,RS232,RS485,Dry contact,Air filter |
Option |
SNMP card,AS400 card,Parallel kit,LBS,Cold start |
Environment |
0-40℃(operation);-25℃~70℃(storage);0-95%(Humidity,non-condensing) |
Dimension |
Cabinet (W*D*H)mm |
600*1000*2000 |
Module(W*D*H)mm |
440*678*86(2U) |
Weight(kg) |
Cabinet(No include batteries) |
260 |
280 |
Module |
23 |
Power module rated capacity |
30KW |